Description
Model |
RSB2A080P7 |
Product or component type |
8-pin Plug-in relay |
Contacts type and composition |
2 C/O |
Contact operation |
Standard |
[Uc] control circuit voltage |
230 V AC 50/60 Hz |
[Ithe] conventional enclosed thermal current |
8 A at -40…40 °C |
Status LED |
Without |
Control type |
Without push-button |
Shape of pin |
Flat (PCB type) |
average coil resistance |
33000 Ohm network: AC at 20 °C +/- 10 % |
[Ue] rated operational voltage |
184…345 V AC 50/60 Hz |
[Ui] rated insulation voltage |
400 V conforming to IEC 60947 |
[Uimp] rated impulse withstand voltage |
3.6 kV conforming to IEC 61000-4-5 |
Contacts material |
Silver alloy (AgNi) |
[Ie] rated operational current |
4 A (AC-1/DC-1) NC conforming to IEC |
8 A (AC-1/DC-1) NO conforming to IEC |
|
Minimum switching current |
10 mA |
Maximum switching voltage |
300 V DC conforming to IEC |
minimum switching voltage |
12 V |
Maximum switching capacity |
2000 VA/224 W |
resistive rated load |
8 A at 250 V AC |
8 A at 28 V DC |
|
Minimum switching capacity |
120 mW at 10 mA, 12 V |
Operating rate |
<= 600 cycles/hour under load |
<= 18000 cycles/hour no-load |
|
Mechanical durability |
5000000 cycles |
Electrical durability |
100000 cycles, 8 A at 250 V, AC-1 NO |
100000 cycles, 4 A at 250 V, AC-1 NC |
|
Operating time |
20 ms operating |
20 ms reset |
|
average coil consumption |
0.75 VA AC |
Drop-out voltage threshold |
>= 0.15 Uc AC |
Safety reliability data |
B10d = 100000 |
Protection category |
RT I |
Test levels |
Level A group mounting |
Operating position |
Any position |