Description
|
Product or component type |
Circuit breaker |
|
Device application |
Distribution |
|
Poles description |
3P |
|
Protected poles description |
3D |
|
Earth leakage protection (Vigi add on) |
Without |
|
[In] rated current |
32 A at 40 °C |
|
network type |
AC |
|
Utilisation category |
Category A |
|
[Icu] Breaking capacity |
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
|
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
|
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
|
Trip unit name |
TM-D |
|
Trip unit technology |
Thermal-magnetic |
|
Trip unit rating |
32 A at 40 °C |
|
Protection type |
Overload protection (thermal) |
|
Short-circuit protection (magnetic) |
|
|
[Uimp] rated impulse withstand voltage |
8 kV conforming to EN/IEC 60947-2 |
|
Network frequency |
50/60 Hz |
|
Breaking capacity code |
B |
|
[Ics] rated service breaking capacity |
15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
|
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
|
|
Mechanical durability |
30000 cycles |
|
Electrical durability |
12000 cycles 415 V In conforming to IEC 60947-2 |
|
Control type |
Toggle |
|
Thermal protection adjustment range |
22.4…32 A |
|
Long time pick-up adjustment type Ir |
Adjustable |
|
Long time pick-up adjustment range |
0.7…1 x In |
|
Long time delay adjustment type |
Fixed |
|
Instantaneous pick-up adjustment type Ii |
Fixed |
|
Instantaneous pick-up adjustment range |
400 A |
|
Contact position indicator |
Yes |
|
Mounting support |
Backplate |
|
Mounting mode |
Fixed |
|
Upside connection |
Front |
|
Downside connection |
Front |
|
Connections – terminals |
Screw connection |
|
Connection pitch |
35 mm |
|
Compatibility code |
CVS100 |
|
Width * Depth * Height |
105 *86 *161 mm |
|
Product weight |
1.5 kg |