| Product name |
EasyPact CVS |
| Device short name |
CVS250B |
| Product or component type |
Circuit breaker |
| Device application |
Distribution |
| Poles description |
3P |
| Protected poles description |
3D |
| Earth leakage protection (Vigi add on) |
Without |
| [In] rated current |
250 A at 40 °C |
| Network type |
AC |
| Utilisation category |
Category A |
| [Icu] Breaking capacity |
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
| 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Trip unit name |
TM-D |
| Trip unit technology |
Thermal-magnetic |
| Trip unit rating |
250 A at 40 °C |
| Protection type |
Short-circuit protection (magnetic) |
| Overload protection (thermal) |