| Model |
RSB2A080BD |
RSB2A080JD |
| Product type |
8-pin Plug-in relay |
8-pin Plug-in relay |
| Contacts type and composition |
2 C/O |
2 C/O |
| Contact operation |
Standard |
Standard |
| [Uc] control circuit voltage |
24 V DC |
12 V DC |
| [Ithe] conventional enclosed thermal current |
8 A at -40…40 °C |
8 A at -40…40 °C |
| Status LED |
Without |
Without |
| Control type |
Without push-button |
Without push-button |
| Shape of pin |
Flat (PCB type) |
Flat (PCB type) |
| average coil resistance |
1440 Ohm network: DC at 20 °C +/- 10 % |
360 Ohm network: AC at 20 °C +/- 10 % |
| [Ue] rated operational voltage |
16.8…36 V DC |
8.4…18 V DC |
| [Ui] rated insulation voltage |
400 V conforming to IEC 60947 |
400 V conforming to IEC 60947 |
| [Uimp] rated impulse withstand voltage |
3.6 kV conforming to IEC 61000-4-5 |
3.6 kV conforming to IEC 61000-4-5 |
| Contacts material |
Silver alloy (AgNi) |
Silver alloy (AgNi) |
| [Ie] rated operational current |
4 A (AC-1/DC-1) NC conforming to IEC |
4 A (AC-1/DC-1) NC conforming to IEC |
| 8 A (AC-1/DC-1) NO conforming to IEC |
8 A (AC-1/DC-1) NO conforming to IEC |
| Minimum switching current |
10 mA |
10 mA |
| Maximum switching voltage |
300 V DC conforming to IEC |
300 V DC conforming to IEC |
| minimum switching voltage |
12 V |
12 V |
| Maximum switching capacity |
2000 VA/224 W |
2000 VA/224 W |
| resistive rated load |
8 A at 250 V AC |
8 A at 250 V AC |
| 8 A at 28 V DC |
8 A at 28 V DC |
| Minimum switching capacity |
120 mW at 10 mA, 12 V |
120 mW at 10 mA, 12 V |
| Operating rate |
<= 600 cycles/hour under load |
<= 600 cycles/hour under load |
| <= 18000 cycles/hour no-load |
<= 18000 cycles/hour no-load |
| Mechanical durability |
30000000 cycles |
30000000 cycles |
| Electrical durability |
100000 cycles, 8 A at 250 V, AC-1 NO |
100000 cycles, 8 A at 250 V, AC-1 NO |
| 100000 cycles, 4 A at 250 V, AC-1 NC |
100000 cycles, 4 A at 250 V, AC-1 NC |
| Operating time |
20 ms operating |
20 ms operating |
| 20 ms reset |
20 ms reset |
| Marking |
CE |
CE |
| average coil consumption |
0.45 W DC |
0.45 W DC |
| Drop-out voltage threshold |
>= 0.1 Uc DC |
>= 0.1 Uc DC |
| Safety reliability data |
B10d = 100000 |
B10d = 100000 |
| Protection category |
RT I |
RT I |
| Test levels |
Level A group mounting |
Level A group mounting |
| Operating position |
Any position |
Any position |