Schneider Emergency stop switching off, metal, red mushroom Ø40, Ø22, 1 NC - XB4BS9442


Price:
Sale priceLE 1,710.00

Description

Product type

Emergency switching off push-button

Bezel material

Chromium plated metal

Fixing collar material

Zamak

Mounting diameter

22.5 mm

Shape of signaling unit head

Round

Type of operator

trigger action and mechanical latching

Head type

Standard

Reset

Key release

Operator profile

Red mushroom Ø 40 mm, unmarked

Type of keylock

Key 455

Key withdrawal position

Center

Contact operation

Slow-break

Connections – terminals

Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1 Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to IEC 60947-1

Height * Width * Depth

47 * 40 * 104  mm

Terminals description ISO n°1

(21-22)NC

Net weight

0.133 kg

Resistance to high pressure washer

7000000 Pa at 55 °C, distance : 0.1 m

Contacts type and composition

1 NC

Contacts usage

Standard contacts

Positive opening

With conforming to IEC 60947-5-1 appendix K

Operating travel

1.5 mm (NC changing electrical state)

4.3 mm (total travel)

Mechanical durability

300000 cycles

Tightening torque

0.8…1.2 N.m conforming to IEC 60947-1

Shape of screw head

Cross compatible with Philips no 1 screwdriver

Cross compatible with pozidriv No 1 screwdriver

Slotted compatible with flat Ø 4 mm screwdriver

Slotted compatible with flat Ø 5.5 mm screwdriver

Contacts material

Silver alloy (Ag/Ni)

Short-circuit protection

10 A cartridge fuse type gG conforming to IEC 60947-5-1

[Ith] conventional free air thermal current

10 A conforming to IEC 60947-5-1

[Ui] rated insulation voltage

600 V (pollution degree 3) conforming to IEC 60947-1

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-1

[Ie] rated operational current

3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1

6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1

0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1

0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1

0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1

1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1

Electrical durability

1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C

1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C

1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C

1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C

1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C

Electrical reliability

Λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to IEC 60947-5-4

Λ < 10exp(-8) at 17 V and 5 mA in clean environment conforming to IEC 60947-5-4