| Device application |
Distribution |
| Product or component type |
Miniature circuit-breaker |
| Poles description |
2P |
| Number of protected poles |
2 |
| [In] rated current |
6 A -63 A 30 °C |
| Network type |
AC |
| Trip unit technology |
Thermal-magnetic |
| Curve code |
C |
| Breaking capacity |
6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| Suitability for isolation |
Yes conforming to EN/IEC 60898-1 |
| Standards |
EN/IEC 60898-1 |
| Network frequency |
50/60 Hz |
| Magnetic tripping limit |
5…10 x In |
| [Ics] rated service breaking capacity |
6000 A 100 % conforming to EN/IEC 60898-1 – 230 V AC 50/60 Hz |
| Limitation class |
3 conforming to EN/IEC 60898-1 |
| [Ui] rated insulation voltage |
440 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| [Uimp] rated impulse withstand voltage |
4 kV conforming to EN/IEC 60898-1 |
| Contact position indicator |
No |
| control type |
Toggle |
| local signalling |
ON/OFF indication |
| Mounting mode |
Clip-on |
| mounting support |
DIN rail |
| 9 mm pitches |
4 |
| Colour |
White |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|