| Product or component type |
Plug-in relay |
| Contacts type and composition |
2 C/O |
| [Uc] control circuit voltage |
230 V AC 50/60 Hz |
| Status LED |
Without |
| Control type |
Lockable test button |
| Utilisation coefficient |
20% |
| Shape of pin |
Flat |
| [Ui] rated insulation voltage |
250 V conforming to IEC |
| 300 V conforming to CSA |
| 300 V conforming to UL |
| [Uimp] rated impulse withstand voltage |
4 kV during 1.2/50 µs |
| Contacts material |
AgNi |
| [Ie] rated operational current |
12 A at 28 V (DC) NO conforming to IEC |
| 12 A at 250 V (AC) NO conforming to IEC |
| 6 A at 28 V (DC) NC conforming to IEC |
| 6 A at 250 V (AC) NC conforming to IEC |
| 12 A at 28 V (DC) conforming to UL |
| 12 A at 277 V (AC) conforming to UL |
| Continuous output current |
10:00 AM |
| Maximum switching voltage |
250 V conforming to IEC |
| resistive rated load |
12 A at 250 V AC |
| 12 A at 28 V DC |
| Maximum switching capacity |
3000 VA/336 W |
| Minimum switching capacity |
170 mW at 10 mA, 17 V |
| Operating rate |
<= 1200 cycles/hour under load |
| <= 18000 cycles/hour no-load |
| Mechanical durability |
10000000 cycles |
| Electrical durability |
100000 cycles for resistive load |
| average coil consumption in VA |
1.2 at 60 Hz |
| Average consumption |
1.2 VA at 60 Hz |
| Drop-out voltage threshold |
>= 0.15 Uc |
| operate time |
20 ms |
| release time |
20 ms |
| average coil resistance |
15000 Ohm at 20 °C +/- 15 % |
| Rated operational voltage limits |
184…253 V AC |
| Safety reliability data |
B10d = 100000 |
| Protection category |
RT I |
| Test levels |
Level A group mounting |
| Operating position |
Any position |
| Net weight |
0.037 kg |