Description
Model |
GV3P40 |
GV3P50 |
product type |
Motor circuit breaker |
Motor circuit breaker |
Device application |
Motor protection |
Motor protection |
Trip unit technology |
Thermal-magnetic |
Thermal-magnetic |
poles description |
3P |
3P |
Network type |
AC |
AC |
Utilisation category |
AC-3 conforming to IEC 60947-4-1 |
AC-3 conforming to IEC 60947-4-1 |
Network frequency |
50/60 Hz conforming to IEC 60947-4-1 |
50/60 Hz conforming to IEC 60947-4-1 |
Fixing mode |
35 mm symmetrical DIN rail: clipped |
35 mm symmetrical DIN rail: clipped |
Panel: screwed (with 3 x M4 screws) |
Panel: screwed (with 3 x M4 screws) |
|
Motor power kW |
18.5 kW at 400/415 V AC 50/60 Hz |
22 kW at 400/415 V AC 50/60 Hz |
22 kW at 500 V AC 50/60 Hz |
30 kW at 500 V AC 50/60 Hz |
|
37 kW at 690 V AC 50/60 Hz |
45 kW at 690 V AC 50/60 Hz |
|
Breaking capacity |
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service short-circuit breaking capacity |
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
Control type |
Rotary handle |
Rotary handle |
[In] rated current |
40 A |
50 A |
Thermal protection adjustment range |
30…40 A conforming to IEC 60947-4-1 |
37…50 A conforming to IEC 60947-4-1 |
Magnetic tripping current |
560 A |
700 A |
[Ith] conventional free air thermal current |
40 A conforming to IEC 60947-4-1 |
50 A conforming to IEC 60947-4-1 |
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2 |
6 kV conforming to IEC 60947-2 |
Phase failure sensitivity |
Yes conforming to IEC 60947-4-1 |
Yes conforming to IEC 60947-4-1 |
Suitability for isolation |
Yes conforming to IEC 60947-1 |
Yes conforming to IEC 60947-1 |
Power dissipation per pole |
8 W |
8 W |
Mechanical durability |
50000 cycles |
50000 cycles |
Electrical durability |
50000 cycles for AC-3 at 415 V In |
50000 cycles for AC-3 at 415 V In |
Rated duty |
Continuous conforming to IEC 60947-4-1 |
Continuous conforming to IEC 60947-4-1 |
Tightening torque |
5 N.m – on screw clamp terminal |
5 N.m – on screw clamp terminal |
Width * Height * Depth |
55 * 132 * 136 mm |
55 * 132 * 136 mm |
net weight |
0.96 kg |
0.96 kg |
Colour |
Dark grey |