Schneider Motor circuit breaker, GV3, 3P, thermal magnetic, EverLink terminals


AMP: 30 - 40
Price:
Sale priceLE 9,730.00

Description

Model

GV3P40

GV3P50

product  type

Motor circuit breaker

Motor circuit breaker

Device application

Motor protection

Motor protection

Trip unit technology

Thermal-magnetic

Thermal-magnetic

poles description

3P

3P

Network type

AC

AC

Utilisation category

AC-3 conforming to IEC 60947-4-1

AC-3 conforming to IEC 60947-4-1

Network frequency

50/60 Hz conforming to IEC 60947-4-1

50/60 Hz conforming to IEC 60947-4-1

Fixing mode

35 mm symmetrical DIN rail: clipped

35 mm symmetrical DIN rail: clipped

Panel: screwed (with 3 x M4 screws)

Panel: screwed (with 3 x M4 screws)

Motor power kW

18.5 kW at 400/415 V AC 50/60 Hz

22 kW at 400/415 V AC 50/60 Hz

22 kW at 500 V AC 50/60 Hz

30 kW at 500 V AC 50/60 Hz

37 kW at 690 V AC 50/60 Hz

45 kW at 690 V AC 50/60 Hz

Breaking capacity

100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2

100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2

50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2

50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2

12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service short-circuit breaking capacity

100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2

100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2

100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2

100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2

50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2

50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2

50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Control type

Rotary handle

Rotary handle

[In] rated current

40 A

50 A

Thermal protection adjustment range

30…40 A conforming to IEC 60947-4-1

37…50 A conforming to IEC 60947-4-1

Magnetic tripping current

560 A

700 A

[Ith] conventional free air thermal current

40 A conforming to IEC 60947-4-1

50 A conforming to IEC 60947-4-1

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

690 V AC 50/60 Hz conforming to IEC 60947-2

[Ui] rated insulation voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-2

6 kV conforming to IEC 60947-2

Phase failure sensitivity

Yes conforming to IEC 60947-4-1

Yes conforming to IEC 60947-4-1

Suitability for isolation

Yes conforming to IEC 60947-1

Yes conforming to IEC 60947-1

Power dissipation per pole

8 W

8 W

Mechanical durability

50000 cycles

50000 cycles

Electrical durability

50000 cycles for AC-3 at 415 V In

50000 cycles for AC-3 at 415 V In

Rated duty

Continuous conforming to IEC 60947-4-1

Continuous conforming to IEC 60947-4-1

Tightening torque

5 N.m – on screw clamp terminal

5 N.m – on screw clamp terminal

Width * Height * Depth

55 * 132 * 136 mm

55 * 132 * 136 mm

net weight

0.96 kg

0.96 kg

Colour

Dark grey

Dark grey