Description
Relay type |
Multifunction control relay |
Product or component type |
3-phase control relay |
Relay name |
RM17TE |
Relay monitored parameters |
Undervoltage and overvoltage in window mode |
Asymmetry |
|
Phase sequence |
|
Phase failure detection |
|
time delay |
Adjustable 0.1…10 s, +/- 10 % of the full scale value Tt- time delay upon fault |
Output contacts |
1 C/O |
Nominal output current |
5:00 AM |
[Uc] control circuit voltage |
208…480 V |
[Un] rated nominal voltage |
, self-powered |
Supply voltage limits |
183…528 V AC |
Reset time |
1500 ms time delay |
Maximum switching voltage |
250 V AC |
250 V DC |
|
Switching capacity in VA |
1250 VA |
Minimum switching current |
10 mA at 5 V DC |
Maximum switching current |
5 A AC |
5 A DC |
|
Control circuit voltage limits |
– 12 % + 10 % Un |
Power consumption in VA |
0…22 VA at 400 V AC 50 Hz |
Control circuit frequency |
50…60 Hz +/- 10 % |
Hysteresis |
2% |
delay at power up |
650 ms |
Maximum measuring cycle |
150 ms measurement cycle as true rms value |
Voltage range |
208…480 V phase to phase |
Repeat accuracy |
0.5 % for input and measurement circuit |
3 % for time delay |
|
Measurement error |
< 0.05 %/°C with temperature variation |
< 1 % over the whole range with voltage variation |
|
Response time |
< 200 ms (in the event of a fault) |
Operating position |
Any position without derating |
Housing material |
Self-extinguishing plastic |
Local signalling |
LED (green) for power ON |
LED (yellow) for relay ON |
|
Mounting support |
35 mm symmetrical DIN rail conforming to IEC 60715 |
Electrical durability |
100000 cycles |
Mechanical durability |
30000000 cycles |
Operating rate |
<= 360 operations/hour full load |
Control type |
Without test button |