Schneider Selector switch, metal, black, Ø22, 2 positions, stay put, 1 NO - XB4BD21


Price:
Sale priceLE 600.00

Description

Product type

Selector switch

Bezel material

Chromium plated metal

Fixing collar material

Zamak

Mounting diameter

22.5 mm

Head type

Standard

Shape of signaling unit head

Round

Type of operator

stay put

Operator profile

Black standard handle

Operator position information

2 positions 90°

Contacts type and composition

1 NO

Contact operation

Slow-break

Connections – terminals

Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1 Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to IEC 60947-1

Height

47 mm

Width

30 mm

Depth

68 mm

Terminals description ISO n°1

(13-14)NO

Net weight

0.095 kg

Resistance to high pressure washer

7000000 Pa at 55 °C, distance : 0.1 m

Contacts usage

Standard contacts

Positive opening

Without

Torque value

0.14 N.m NO changing electrical state

Mechanical durability

1000000 cycles

Tightening torque

0.8…1.2 N.m conforming to IEC 60947-1

Shape of screw head

Cross compatible with Philips no 1 screwdriver

Cross compatible with pozidriv No 1 screwdriver

Slotted compatible with flat Ø 4 mm screwdriver

Slotted compatible with flat Ø 5.5 mm screwdriver

Contacts material

Silver alloy (Ag/Ni)

Short-circuit protection

10 A cartridge fuse type gG conforming to IEC 60947-5-1

[Ith] conventional free air thermal current

10 A conforming to IEC 60947-5-1

[Ui] rated insulation voltage

600 V (pollution degree 3) conforming to IEC 60947-1

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-1

[Ie] rated operational current

3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1

6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1

0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1

0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1

0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1

1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1

Electrical durability

1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C

1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C

1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C

1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C

1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C

Electrical reliability

Λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to IEC 60947-5-4

Λ < 10exp(-8) at 17 V and 5 mA in clean environment conforming to IEC 60947-5-4