Product type |
Selector switch |
Bezel material |
Chromium plated metal |
Fixing collar material |
Zamak |
Mounting diameter |
22.5 mm |
Head type |
Standard |
Shape of signaling unit head |
Round |
Type of operator |
stay put |
Operator profile |
Black standard handle |
Operator position information |
3 positions +/- 45° |
Contacts type and composition |
2 NO |
Contact operation |
Slow-break |
Connections – terminals |
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1 Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to IEC 60947-1 |
Height * Width * Depth |
47 * 30 * 68 mm |
Terminals description ISO n°1 |
(23-24)NO |
(13-14)NO |
|
Net weight |
0.105 kg |
Resistance to high pressure washer |
7000000 Pa at 55 °C, distance : 0.1 m |
Contacts usage |
Standard contacts |
Positive opening |
Without |
Torque value |
0.14 N.m NO changing electrical state |
Mechanical durability |
1000000 cycles |
Tightening torque |
0.8…1.2 N.m conforming to IEC 60947-1 |
Shape of screw head |
Cross compatible with Philips no 1 screwdriver |
Cross compatible with pozidriv No 1 screwdriver |
|
Slotted compatible with flat Ø 4 mm screwdriver |
|
Slotted compatible with flat Ø 5.5 mm screwdriver |
|
Contacts material |
Silver alloy (Ag/Ni) |
Short-circuit protection |
10 A cartridge fuse type gG conforming to IEC 60947-5-1 |
[Ith] conventional free air thermal current |
10 A conforming to IEC 60947-5-1 |
[Ui] rated insulation voltage |
600 V (pollution degree 3) conforming to IEC 60947-1 |
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-1 |
[Ie] rated operational current |
3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1 |
6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1 |
|
0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1 |
|
0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1 |
|
0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1 |
|
1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1 |
|
Electrical durability |
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C |
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C |
|
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C |
|
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C |
|
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN 60947-5-1 appendix C |
|
Electrical reliability |
Λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to IEC 60947-5-4 |
Λ < 10exp(-8) at 17 V and 5 mA in clean environment conforming to IEC 60947-5-4 |