Description
Specification |
LC1D40AM7 |
LC1D50AM7 |
LC1D65AM7 |
Coil Voltage (Control) |
220 V AC 50/60 Hz |
220 V AC 50/60 Hz |
220 V AC 50/60 Hz |
Rated Operational Voltage (Ue) |
Power circuit: ≤ 690 V AC 25–400 Hz / ≤ 300 V DC |
Power circuit: ≤ 690 V AC 25–400 Hz / ≤ 300 V DC |
Power circuit: ≤ 690 V AC 25–400 Hz / ≤ 300 V DC |
Rated Current (Ie) – AC-1 |
60 A (≤ 440 V AC, < 60 °C) |
80 A (≤ 440 V AC, < 60 °C) |
80 A (≤ 440 V AC, < 60 °C) |
Rated Current (Ie) – AC-3 |
40 A (≤ 440 V AC, < 60 °C) |
50 A (≤ 440 V AC, < 60 °C) |
65 A (≤ 440 V AC, < 60 °C) |
Motor Power Rating (kW) |
18.5 kW at 380–400 V AC 50/60 Hz (AC-3); 11 kW at 220–230 V AC 50/60 Hz (AC-3); 22 kW at 415–440 V AC 50/60 Hz (AC-3); 22 kW at 500 V AC 50/60 Hz (AC-3); 30 kW at 660–690 V AC 50/60 Hz (AC-3) |
15 kW at 220–230 V AC 50/60 Hz (AC-3); 22 kW at 380–400 V AC (AC-3); 25 kW at 415 V AC (AC-3); 30 kW at 440 V AC (AC-3); 30 kW at 500 V AC (AC-3); 33 kW at 660–690 V AC (AC-3) |
18.5 kW at 220–230 V AC (AC-3); 30 kW at 380–400 V AC (AC-3); 37 kW at 500 V AC (AC-3); 37 kW at 660–690 V AC (AC-3) |
Number of Poles |
3P |
3P |
3P |
Auxiliary Contacts |
1 NO + 1 NC (mechanically linked, mirror contact) |
1 NO + 1 NC (mechanically linked, mirror contact) |
1 NO + 1 NC (mechanically linked, mirror contact) |
Utilization Category |
AC-1, AC-3, AC-3e, AC-4 |
AC-1, AC-3, AC-3e, AC-4 |
AC-1, AC-3, AC-3e, AC-4 |
Mechanical Life |
6 million operations |
6 million operations |
6 million operations |
Electrical Life |
1.4 million operations (60 A AC-1 ≤ 440 V); 1.5 million operations (40 A AC-3 ≤ 440 V) |
1.1 million operations (80 A AC-1 ≤ 440 V); 1.45 million operations (50 A AC-3 ≤ 440 V); 1.45 million operations (50 A AC-3e ≤ 440 V) |
1.4 million operations (80 A AC-1 ≤ 440 V); 1.45 million operations (65 A AC-3 ≤ 440 V) |
Making / Breaking Capacity |
800 A at 440 V (Power circuit, IEC 60947) |
900 A at 440 V (IEC 60947) |
1000 A at 440 V (IEC 60947) |
Operating Temperature Range |
−40 … 60 °C (up to 70 °C with derating) |
−40 … 60 °C (up to 70 °C with derating) |
−40 … 60 °C (up to 70 °C with derating) |
Rated Insulation Voltage (Ui) |
Power circuit: 690 V (IEC 60947-4-1); 600 V (CSA/UL) |
690 V (IEC 60947-4-1) |
690 V (IEC 60947-4-1); 600 V (CSA/UL) |
Protection Degree (IP) |
IP20 (front face, IEC 60529) |
IP20 (front face, IEC 60529) |
IP20 (front face, IEC 60529) |
Mounting Type |
Plate or Rail |
Plate or Rail |
Plate or Rail |
Standards / Certifications |
IEC 60947-4-1, IEC 60947-5-1, EN 60947-4-1, EN 60947-5-1, CSA C22.2 No 14, UL 60947-4-1, IEC 60335-2-40 Annex JJ, UL 60335-2-40 Annex JJ, IEC 60335-1 Clause 30.2; Certifications: CCC, UL, CB Scheme, CSA, CE, UKCA, Marine, EAC |
EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, IEC 60335-1/-2-40, UL 60947-4-1, UL 60335-2-40, CSA C22.2 No 14; Certifications: CE, UKCA, CCC, CB Scheme, Marine, EAC |
EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, CSA C22.2 No 14, UL 60947-4-1, IEC 60335-2-40 Annex JJ, UL 60335-2-40 Annex JJ, IEC 60335-1 Clause 30.2; Certifications: CCC, UL, CB Scheme, CSA, CE, UKCA, Marine, EAC |