Schneider TeSys Contactor | 3 Pole (1 NO + 1 NC ) – 24 V AC Coil


AMP: 18 A
Price:
Sale priceLE 1,760.00

Description

Specification

LC1D18B7 – 18 A

LC1D25B7 – 25 A

Coil Voltage (Control)

24 V AC, 50/60 Hz

24 V AC, 50/60 Hz

Rated Operational Voltage (Ue)

≤ 690 V AC (25–400 Hz) / ≤ 300 V DC

≤ 690 V AC (25–400 Hz) / ≤ 300 V DC

Rated Current (Ie) – AC-1

32 A @ ≤ 440 V AC, 60 °C

40 A @ ≤ 440 V AC, 60 °C

Rated Current (Ie) – AC-3

18 A @ ≤ 440 V AC, 60 °C

25 A @ ≤ 440 V AC, 60 °C

Motor Power Rating (kW)

4 kW @ 220–230 V • 7.5 kW @ 380–400 V • 9 kW @ 415–440 V • 10 kW @ 500 V • 10 kW @ 660–690 V

5.5 kW @ 220–230 V • 11 kW @ 380–400 V • 15 kW @ 500 V • 15 kW @ 660–690 V

Number of Poles

3-pole (3 NO main contacts)

3-pole (3 NO main contacts)

Auxiliary Contacts

1 NO + 1 NC

1 NO + 1 NC

Utilization Category

AC-1, AC-3, AC-4

AC-1, AC-3, AC-4

Mechanical Life

15 million operations

15 million operations

Electrical Life

1.65 million operations @ 18 A AC-3

1.65 million operations @ 25 A AC-3

Making / Breaking Capacity

300 A @ 440 V AC

450 A @ 440 V AC

Operating Temperature Range

–40 … 60 °C (up to 70 °C with derating)

–40 … 60 °C (up to 70 °C with derating)

Rated Insulation Voltage (Ui)

690 V AC (IEC 60947-4-1)

690 V AC (IEC 60947-4-1)

Protection Degree (IP)

IP20 (front face)

IP20 (front face)

Mounting Type

DIN rail or plate

DIN rail or plate

Standards / Certifications

IEC 60947-4-1/5-1, UL, CSA, CCC, UKCA, EAC

IEC 60947-4-1/5-1, UL, CSA, CCC, UKCA, EAC