Description
| Range | TeSys TeSys Deca |
|---|---|
| Device short name | GVAN |
| Product or component type | Auxiliary contact block |
| Product compatibility | GV2P GV2L GV2ME GV2LE GV2RT GV2LM GV3P GV3L |
| Mounting location | Left side |
| Pole contact composition | 1 NO + 1 NC |
| [Ui] rated insulation voltage | 600 V conforming to UL 508 690 V conforming to IEC 60947-1 600 V conforming to CSA C22.2 No 14 |
|---|---|
| [Ue] rated operational voltage | 48...690 V AC 24...240 V DC |
| [Ith] conventional free air thermal current | 6 A |
| Mechanical durability | 100000 cycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Protection type | GB2CB... circuit breaker GG fuse 10 A |
| Rated operational power in VA | 300 VA at 48 V AC-15 - electrical durability: 100000 cycles 414 VA at 690 V AC-15 - electrical durability: 100000 cycles 500 VA at 110…127 V AC-15 - electrical durability: 100000 cycles 500 VA at 500 V AC-15 - electrical durability: 100000 cycles 650 VA at 440 V AC-15 - electrical durability: 100000 cycles 720 VA at 230…240 V AC-15 - electrical durability: 100000 cycles 850 VA at 380…415 V AC-15 - electrical durability: 100000 cycles |
| Rated operational power in W | 120 W at 240 V DC-13 - electrical durability: 100000 cycles 140 W at 110 V DC-13 - electrical durability: 100000 cycles 140 W at 24 V DC-13 - electrical durability: 100000 cycles 180 W at 60 V DC-13 - electrical durability: 100000 cycles 240 W at 48 V DC-13 - electrical durability: 100000 cycles |
| Tightening torque | 1.4 N.m screw clamp terminals |
| Height | 89 mm |
| Width | 9.3 mm |
| Depth | 66 mm |
| Net weight | 0.05 kg |
| Colour | Dark grey |